• High Power Laser and Particle Beams
  • Vol. 33, Issue 6, 065013 (2021)
Tingbiao Ma1, Li’ang Chen2, Mingming Xu3, Hui Chen2, Guowei Ge2, and Xian Cheng2
Author Affiliations
  • 1Henan Jiuyu Enpai Power Technology Co., Ltd., Zhengzhou 450052, China
  • 2College of Electrical Engineering, Zhengzhou University, Zhengzhou 450001, China
  • 3Electric Power Research Institute of State Grid Henan Electric Power Co., Ltd., Zhengzhou 450052, China
  • show less
    DOI: 10.11884/HPLPB202133.210071 Cite this Article
    Tingbiao Ma, Li’ang Chen, Mingming Xu, Hui Chen, Guowei Ge, Xian Cheng. Probe diagnostics of post-arc residual plasma of vacuum circuit breakers[J]. High Power Laser and Particle Beams, 2021, 33(6): 065013 Copy Citation Text show less

    Abstract

    The post-arc residual plasma of the vacuum arcs in the breaking process is an important parameter, which is used to indicate the breaking capacity of the vacuum circuit breakers. Based on the basic principle of the electron saturation region for the probe diagnostics, the paper proposes a measuring method of electron density in residual plasma. The structure and principle of the method are analyzed. The probe structure and control system of the probe diagnostics are designed. The electron density of the residual plasma is measured by the single probe based on the dismountable vacuum chamber. The vacuum arcs development is observed by the high speed camera. The influence of the current magnitude and contact structure on the decay process of the residual plasma is investigated. Finally, the validity of the measurement method is verified by comparing with other diagnostic methods, which provides a low-cost and effective diagnostic method for future research on the micro-characteristics of vacuum circuit breakers.
    Tingbiao Ma, Li’ang Chen, Mingming Xu, Hui Chen, Guowei Ge, Xian Cheng. Probe diagnostics of post-arc residual plasma of vacuum circuit breakers[J]. High Power Laser and Particle Beams, 2021, 33(6): 065013
    Download Citation