• Acta Photonica Sinica
  • Vol. 52, Issue 3, 0352120 (2023)
Lingyan CAO1, Zhijun LI1, Hongchao QI2, Jikuang ZHAO2..., Chenxi LI2 and Ke CHEN2,*|Show fewer author(s)
Author Affiliations
  • 1Guodian Nanjing Automation co., LTD., Nanjing 210032, China
  • 2School of Optoelectronic Engineering and Instrumentation Science, Dalian University of Technology, Dalian 116024, China
  • show less
    DOI: 10.3788/gzxb20235203.0352120 Cite this Article
    Lingyan CAO, Zhijun LI, Hongchao QI, Jikuang ZHAO, Chenxi LI, Ke CHEN. Ultra-high Sensitivity Detection Technology of Dissolved Gas in Oil Based on Miniature Resonant Photoacoustic Cell[J]. Acta Photonica Sinica, 2023, 52(3): 0352120 Copy Citation Text show less
    Structural diagram of the miniature resonant photoacoustic cell
    Fig. 1. Structural diagram of the miniature resonant photoacoustic cell
    Simulated frequency response of the photoacoustic cell
    Fig. 2. Simulated frequency response of the photoacoustic cell
    Structure diagram of vacuum degassing module
    Fig. 3. Structure diagram of vacuum degassing module
    Schematic diagram of the dissolved gas detection system based on miniature resonant photoacoustic cell
    Fig. 4. Schematic diagram of the dissolved gas detection system based on miniature resonant photoacoustic cell
    Absorption spectra in the near-infrared band of 1 μL/L C2H2,500 μL/L CO2 and 1 000 μL/L H2O
    Fig. 5. Absorption spectra in the near-infrared band of 1 μL/L C2H2,500 μL/L CO2 and 1 000 μL/L H2O
    Experimental frequency response of the micro-resonant photoacoustic cell
    Fig. 6. Experimental frequency response of the micro-resonant photoacoustic cell
    Relationship between the photoacoustic signal amplitude and the modulation current
    Fig. 7. Relationship between the photoacoustic signal amplitude and the modulation current
    The second harmonic response of the system to dissolved C2H2 oil samples with different concentrations
    Fig. 8. The second harmonic response of the system to dissolved C2H2 oil samples with different concentrations
    The relationship between the peak values of second harmonic signals and the oil sample concentrations
    Fig. 9. The relationship between the peak values of second harmonic signals and the oil sample concentrations
    Concentration/(μL·L-1Result of test 1/(μL·L-1Result of test 2/(μL·L-1Result of test 3/(μL·L-1Maximum error/(μL·L-1
    5.65.75.55.40.2
    1.81.71.71.90.1
    0.20.30.20.30.1
    Table 1. Detection results of dissolved C2H2 in low concentration oil
    Lingyan CAO, Zhijun LI, Hongchao QI, Jikuang ZHAO, Chenxi LI, Ke CHEN. Ultra-high Sensitivity Detection Technology of Dissolved Gas in Oil Based on Miniature Resonant Photoacoustic Cell[J]. Acta Photonica Sinica, 2023, 52(3): 0352120
    Download Citation